There are many decisions that designers face when specifying a BAS, including:
- What control strategies to implement;
- Extent of the control to be provided by the BAS;
- Type of communications protocols to utilize; and
- Use of a web browser interface and Internet communications.
Energy-saving control strategies
Here is a list of the most common strategies that building automation systems employ in order to use energy more efficiently.
Scheduling. Scheduling is the practice of turning equipment on or off depending on time of day, day of the week, day type, or other variables, such as outside air conditions. Improving equipment schedules is one of the most common and effective measures for saving energy in commercial buildings. A feature called "Optimum Start," offered by all BAS manufacturers, can increase energy savings by automatically starting a system no earlier than necessary based on daily variations in the weather.
Lockouts. Lockouts ensure that equipment does not come on unless necessary. They protect against nuances in the programming of the control system that may inadvertently cause equipment to turn on. For example, a chiller and its associated pumps can be locked out according to a calendar date, when the outside air falls below a certain temperature, or when building cooling requirements are below a minimum.
Resets. HVAC systems typically use less energy when their operating parameters are adjusted to meet the building load. Because this load varies with the weather, a BAS can help equipment to operate at greater efficiency levels by automatically varying these operating parameters. The simplest approach is to use a proportional reset schedule based on outdoor temperature (Figure 2). Although that method works reasonably well, a more effective method is to base resets directly on building loads (Figure 3). Examples of building control parameters that can be reset include supply-air and discharge-air temperature for fan systems that use terminal reheat, hot-deck and cold-deck temperatures for multizone HVAC systems, and heating-water supply temperature.
Figure 3: Direct load information reset
In this reset schedule, the cooling load is based on the number of chilled water valves that are greater than 90 percent open.
Direct digital control (DDC). All modern BASs use DDC technology—solid-state sensors and controllers that control valves, dampers, and other system components. Until the 1980s, pneumatic controls, which operate using compressed air, dominated the market. But pneumatic systems are more prone to failure and require more calibration and maintenance to ensure a clean and dry source of compressed air for controlling components such as actuators.
DDC systems also use a more advanced control algorithm called PID (or proportional-integral-derivative) that can be implemented in the BAS’s computer code. Due to the complexity of this algorithm, older pneumatic or electronic controls used only the proportional form of this control technique, which is known for its inability to reliably maintain the temperature setpoint. If applied properly, PID can both save energy and provide improved comfort. However, note that proper implementation of a PID control algorithm is a complex process that is best left to experienced professionals.
Demand limiting. Because electrical demand charges can comprise 40 percent or more of a utility bill, many building automation systems can benefit from demand-limiting or load-shedding functions. For example, when the demand on a building meter or piece of equipment, such as a chiller, approaches a predetermined setpoint, the BAS does not allow the equipment to load up any further. In buildings with electric heat, electrical demand charges can be reduced if the heat is staged on in the morning over a several-hour period starting with the coldest spaces first. Other demand-limiting strategies are expected to be developed as utilities implement time-of-day or real-time electrical pricing in their rate structures.
Diagnostics. Building operators who use a BAS to monitor information such as temperatures, air and water flows and pressures, and actuator positions may use that data to determine whether equipment is operating incorrectly or inefficiently and to troubleshoot problems. A thorough job of building diagnostics typically requires the building operator to monitor more points than the minimal number needed to simply control a building, but a modern BAS gives users a good head start on a recommissioning or ongoing commissioning program. A modern BAS helped personnel from Texas A&M's Energy Systems Laboratory to cut energy bills at a state office building by 27 percent. The BAS helped to implement nighttime shutdowns and chart actual building temperatures to identify opportunities for temperature setback during unoccupied hours.
Extent of control provided by the BAS
A major BAS design issue for both new and existing buildings is the extent of control provided by the BAS. This issue is handled differently for new buildings than for BAS retrofits in existing buildings:
New buildings. HVAC equipment is often packaged with temperature controls provided by the equipment manufacturer. In many cases, these controls are a necessary part of the equipment and cannot be removed (for example, boiler and chiller operating controls and safety limits). In this case, the BAS can still provide a certain amount of control that will improve the efficiency and comfort of the building. For example, a BAS usually provides chiller, pump, and cooling tower staging for plants with multiple chillers. The BAS can also reset the chiller's operating parameters and monitor other chiller operating conditions. Note that boiler and chiller manufacturers sometimes provide their own "central plant" control systems. These are usually not recommended because they diminish the BAS's capability to perform energy-efficient control and provide diagnostics.
Manufacturer-provided controls for other equipment (for example, air handling units [AHUs], rooftop units, and variable air volume (VAV) boxes) are usually optional. The advantage of using manufacturer-provided controls is that it reduces project costs and can often provide better control (because the controls are designed around the equipment). The disadvantage is that a communications protocol connection to this equipment will be needed to fully allow the BAS to perform energy-efficient supervisory control and provide diagnostics. Even with this communications connection, the manufacturer controls sometimes do not allow the BAS to adequately perform the necessary supervisory control. Because of this, many designs involve the field-installation of BAS controls on HVAC system components.
Existing buildings. Existing buildings with older conventional controls (for example, pneumatic and/or electronic controls) present a different design challenge. The existing hardware may limit the extent to which the BAS can provide system control. This challenge is due to the payback associated with the cost of replacing conventional controls versus the energy-savings benefit provided by the BAS. As a general rule, the use of a BAS to replace existing conventional controls for central equipment (for example, boilers, chillers, and AHUs) usually results in a short energy-savings payback (under five years). On the other hand, replacing conventional controls (typically a pneumatic thermostat) on terminal HVAC equipment (typically VAV boxes or reheat coils) usually involves energy-savings paybacks that can be in the 10-to-20-year range. Note that the improved comfort of building occupants and enhanced ability to monitor, understand, and diagnose malfunctions in the HVAC system often provide value above and beyond the energy savings that a BAS offers.
In general, BASs that provide full DDC (Figure 4) offer many more benefits over systems that use manufacturer-provided controls or depend on older, conventional controls.
Communications protocol
Two major communications choices are available: proprietary and open (or standard).
Systems that rely on proprietary communications are rapidly disappearing from the marketplace. Because a proprietary system does not communicate with other systems, the user’s options for expansion of the BAS are limited. Choices are also reduced for the purchase of new equipment, which limits the user’s bargaining power. However, proprietary systems do offer the advantage of a single source of responsibility when there are problems.
There are several advantages to using an open communications protocol for a BAS. First, there is the assurance that equipment from multiple manufacturers will be able to interact. Using BACnet products that have been listed by BACnet Testing Laboratory ("BTL listed") ensures that they have been tested to confirm compliance with BACnet standards. Using equipment with open protocols also creates a competitive bidding environment for system additions and renovations, which helps to limit costs. This situation also helps keep manufacturers that have on-site equipment from becoming too comfortable and ensures a good level of service and response to problems.
Another advantage is the containment of expenses associated with interfacing the BAS to mechanical equipment. For example, it is normally difficult to extend the features of a BAS with proprietary communications to monitor temperatures, pressures, and flows of a new chiller. If all additions to a system are specified as open protocol, however, interfacing becomes easier and less expensive.
The use of open protocols also reduces the need to run multiple software packages on the BAS workstation or to utilize specialized interface equipment to communicate with devices using different protocols. The result is lower system costs and training expenses, fewer maintenance agreements and spare parts, and a single mode of system access.
The introduction of web browser interfaces is the most important BAS development since the introduction of open communications protocols. Web browser capability is available via a software package (which usually runs on a dedicated web server) or may even be built into the highest-level controllers provided with a BAS. It allows a user to access and view the BAS through the Internet using a computer that is running web browser software. Users can take advantage of this capability to monitor and control the BASs in multiple facilities from a single computer (see Figure 5).